Operation and Maintenance Manual (DTR) iSWAY
®
Set of products
Version 1.8 of 2.2021
157
2.
Any damage to the iSWAY-FC, iSWAY-WFC, iSWAY-RFC or parts thereof (parts of the
SAFETY WAY system) resulting from non-compliance with the guidelines contained in the
documentation will not be subject to warranty repairs.
3.
The iSWAY-FC, iSWAY-WFC, iSWAY-RFC
(SAFETY WAY® system) may only be operated
with the unit not in operation.
18.1.
iSWAY
® Daily test
The iSWAY-FC, iSWAY-WFC, and iSWAY-RFC device performs a daily test automatically
every 24 hours. During each test, the efficiency of the part controlling the aeration fan is tested.
During the test, the opening of the shut-off damper is checked and the fan is started (the inverter
control is set to 10Hz as standard). The total daily test time shall not exceed 1 minute. As a
standard, the daily test is set at 4:09 a.m. (the time may be changed by a SMAY service technician
or by an authorized SMAY service technician), the activation of individual devices is silent and does
not disturb the night's silence.
If the daily test is passed incorrectly, the "Failure" lamp is lit on the TSS/TS panel and the
"Day Test Error" message is displayed on the MSPU. In order to reset the error of the daily test,
reset the device with the switch "Reset SAP Fire" on TSS/TS. In the case of permanent activation
of the "SAP Fire Cancellation" switch, the device will not perform a daily test.
All information about the tests are stored in the flash memory of the MAC-FC controller.
18.2.
Automatic test of the device/system with control of operating
parameters
Automatic testing of the device can be performed by a person who has received SMAY
service training or an authorized SMAY service provider confirmed by a "Training Protocol" for
iSWAY-FC, iSWAY-WFC, iSWAY-RFC devices .
For an automatic test of the iSWAY-FC, iSWAY-WFC, iSWAY-RFC with performance control, it
is necessary to:
1.
Call the fire alarm in the specified area where the fire signal activates iSWAY.
2.
Check that the equipment/system is working satisfactorily - according to the "Fire
Emergency Scenario" for the specific building/system.
3.
Remove the SAP signal from iSWAY-FC, iSWAY-WFC, iSWAY-RFC from the fire detection
and signalling system.
4.
Deactivate the fire signal on the TSS panel or by using the "SAP Fire Cancelation" switch.
The aeration fan should stop working.
5.
Leave the device in standby mode.
Note:
If the system operation deviates from the requirements of the "Fire Incident Development
Scenario" for a specific building/system, the following checks should be carried out:
1.
Check that the device/system has received a fire signal (TSS or TS). In case the indicator
does not signal the reception of the SAP signal, it is necessary to start service activities,
based on the device's technical documentation, aimed at diagnosing and removing failures.