background image

Operating instructions

G3G200-GN18-20

Translation of the original operating instructions

ebm-papst Mulfingen GmbH & Co. KG

Bachmühle 2
D-74673 Mulfingen
Phone +49 (0) 7938 81-0
Fax +49 (0) 7938 81-110
[email protected]
www.ebmpapst.com

CONTENTS

1. SAFETY REGULATIONS AND NOTES

1

1. SAFETY REGULATIONS AND NOTES

Please read these operating instructions carefully before starting to work
with the device. Observe the following warnings to prevent malfunctions
or physical damage to both property and people.
These operating instructions are to be regarded as part of this device.
If the device is sold or transferred, the operating instructions must
accompany it.
These operating instructions may be duplicated and forwarded for
information about potential dangers and their prevention.

1.1 Levels of hazard warnings

1

1.1 Levels of hazard warnings

These operating instructions use the following hazard levels to indicate
potentially hazardous situations and important safety regulations:

DANGER

Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury. Compliance with
the measures is mandatory.

WARNING

Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury. Exercise extreme
caution while working.

CAUTION

Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury or damage of property.

NOTE

A potentially harmful situation can occur and, if not avoided, can
lead to property damage.

1.2 Staff qualification

1

1.2 Staff qualification

Only specialised electrical personnel may install the device, perform the
test run and work on the electrical system.
Only trained and authorised specialist personnel are permitted to
transport, unpack, assemble, operate or maintain the device, or to use it
in any other manner.

1.3 Basic safety rules

1

1.3 Basic safety rules

Any safety hazards stemming from the device must be re-evaluated
once it is installed in the end device.
Observe the following when working on the unit:

;

Do not make any modifications, additions or conversions to the
device without the approval of ebm-papst.

1.4 Electrical voltage

1

1.4 Electrical voltage

;

Check the electrical equipment of the device at regular intervals, refer
to chapter 6.2 Safety test.

;

Replace loose connections and defective cables immediately.

DANGER
Electrical load on the device

Risk of electric shock
→ Stand on a rubber mat if you are working on an electrically

charged device.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

2

1.5 Safety and protective functions

2

1.6 Electromagnetic radiation

2

1.7 Mechanical movement

2

1.8 Deflagration

2

1.9 Emission

2

1.10 Hot surface

2

1.11 Transport

3

1.12 Storage

3

1.13 Disposal

3

2. PROPER USE

5

3. TECHNICAL DATA

5

3.1 Product drawing

6

3.2 Nominal data

6

3.3 Data according to ErP directive

6

3.4 Technical features

6

3.5 Mounting data

6

3.6 Transport and storage conditions

6

3.7 Electromagnetic compatibility

7

4. CONNECTION AND START-UP

7

4.1 Connecting the mechanical system

7

4.2 Connecting the electrical system

9

4.3 Connection screen

10

4.4 Checking the connections

10

4.5 Switch on device

10

4.6 Switching off the device

10

5. INTEGRATED PROTECTIVE FUNCTIONS

11

6. MAINTENANCE, MALFUNCTIONS, POSSIBLE

CAUSES AND REMEDIES

11

6.1 Cleaning

11

6.2 Safety test

Item no. 50363-5-9970 · Revision 68161 · Release 2009-10-09 · Page 1 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G3G200-GN18-20

Page 1: ...are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device m...

Page 2: ...ive parts Escaping gas may also cause explosions Never open the blower WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You cou...

Page 3: ...he operating instructions Using the device in accordance with the permitted ambient temperature see chapter 3 6 Transport and storage conditions and chapter Only using the device in stationary systems...

Page 4: ...ions In addition all application options that are not listed under proper use Item no 50363 5 9970 Revision 68161 Release 2009 10 09 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfin...

Page 5: ...female connector Tyco No 926884 1 1 1 L 1 2 N 1 3 PE 2 5 pole strip to fit mating connector not included in standard scope of delivery Molex No 39 01 4050 female connector Molex No 39 00 0059 2 1 2 2...

Page 6: ...ion any Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Tach output Over temperature protected electronics motor PFC active Motor current limit Li...

Page 7: ...trical voltage The device is a built in component and features no electrically isolating switch Connect the device only to circuits that can be switched off using an all pole disconnecting switch When...

Page 8: ...n Due to the locked rotor protection the start up current LRA is equal to or less than the nominal current FLA Item no 50363 5 9970 Revision 68161 Release 2009 10 09 Page 8 12 ebm papst Mulfingen GmbH...

Page 9: ...e 16 45 VDC residual ripple 3 5 SELV ST2 2 Tach Speed monitoring 3 pulses per revolution SELV ST2 3 0 10 V Control input 0 10 V impedance 100k SELV ST2 4 PWM Control input PWM 1 6 kHz SELV ST2 5 GND G...

Page 10: ...device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for ma...

Page 11: ...if imbalance is still evident after cleaning replace the device If you have attached any weight clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switc...

Page 12: ...Visual inspection At least every 6 months Replace wires Condensate discharge holes for clogging as necessary Visual inspection At least every 6 months Open bore holes Check the ball bearings to ensure...