User Manual of EM730/EM730E Series Inverter
97
options
2: sleep at lower frequency limit
3: sleep with tube sealed
F09.28
Sleep action
point
0.00-100.00 (100.00 corresponds to the PID setting
feedback range)
%
100.00
●
F09.29
Sleep delay
time
0.0 - 6500.0
s
0.0
●
F09.30
Wake-up
action point
0.00-100.00 (100.00 corresponds to the PID setting
feedback range)
%
0.00
●
F09.31
Wake-up
delay time
0.0 - 6500.0
s
0.0
●
F09.32
Multi-segme
nt PID
setting 1
0.0 to PID setting feedback range F09.03
0.0
●
F09.33
Multi-segme
nt PID
setting 2
0.0 to PID setting feedback range F09.03
0.0
●
F09.34
Multi-segme
nt PID
setting 3
0.0 to PID setting feedback range F09.03
0.0
●
F09.35
Upper limit
of feedback
voltage
Lower limit of feedback voltage to 10.00
V
10.00
●
F09.36
Lower limit
of feedback
voltage
0.00 to upper limit of feedback voltage
V
0.00
●
F09.37
Integral
action option
within set
PID change
time
0: Always calculate the integral term
1: Calculate the integral term after the F09.21 set time is
reached
2: Calculate the integral term when the error is less than
F09.38
0
Straight-2
●
F09.38
Integral
within set
PID change
time
Input
deviation
0.00-100.00
%
0
●
F09.39
Wake-up
option
0: target pressure F09.01* coefficient of wake-up action
point
1: Wake-up action point (F09.30)
0
〇
F09.40
Coefficient
of wake-up
0.0-100.0 (100% corresponds to PID setting)
%
90.0
●