User Manual of EM730/EM730E Series Inverter
176
7
Output power
0.00kW to 2*Pe, corresponding to the output 0.0% to
100.0%
8
AI1
Output the actual input voltage, instead of the offset
result.
0.0% to 100.0%, corresponding to the output 0.0% to
100.0%
9
AI2
12
High-frequency
pulse input (with
100% corresponding
to 100.00kHz)
The function codes F02.26-F02.28 correspond to the
output 0.0%-100.0%.
13
Communication
setting 1
Communication setting by M1 terminal, communication
address option 701AH
14
Count value
0 to F16.03, corresponding to the output F16.10 to F16.11
15
Length value
0 to F16.01, corresponding to the output F16.10 to F16.11
16
PID output
percentage
-100.0% to 100.0%, corresponding to the output 0.0% to
100.0%
18
PID feedback
-100.0% to 100.0%, corresponding to the output 0.0% to
100.0%
19
PID setting
-100.0% to 100.0%, corresponding to the output 0.0% to
100.0%
★
Fmax, maximum frequency (F00.16)
Ie, rated current of the inverter (F12.21)
Ue, rated voltage of the inverter (F12.20)
Pe, rated power of the inverter (F12.19)
The output physical quantity of the analog output terminal can be switched between the
voltage signal (0.00V to 10.00V) and current signal (0.00mA to 20.00mA) via the jumper cap
For the voltage signal output, the value from 0.0% to 100.0% corresponds to the output 0.00V to
10.00V. For the current signal output, the value from 0.0% to 100.0% corresponds to the output
0.00mA to 20.00mA.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F03.27
M1 output bias
-100.0 - 100.0
%
0.0
●
F03.28
M1 output gain
-10.00 - 10.00
1.00
●
The above function codes are usually used to correct the zero drift of analog output and the
deviation of output amplitude. They can also be used to customize the required AO output curve
to meet the requirements of different instruments or others. If the offset is represented by “b”,