User Manual of EM730/EM730E Series Inverter
245
For the digital potentiometer setting, see the setting of the main frequency source A.
F12.45
UP/DOW
N function
options of
keyboard
D7 D6 D5
D4
D3
D2
D1
D0
00000
〇
*
*
*
Communication
High-speed
pulse
Analog
quantity
Digital
frequency
Multi-
segment
speed
0: Invalid
1: valid
Select the up/down function in the corresponding frequency setting mode.
If the default frequency source is the digital frequency:
In case of F12.45 = 00000, the UP/DOWN function is unavailable, and the set frequency
cannot be changed by the digital potentiometer in the monitoring status.
In case of F12.45 = 00010, the UP/DOWN function is available, and the set frequency of
the main channel can be changed by the digital potentiometer in the monitoring status.
7.14
Torque Control Parameter Group of F13 Group
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F13.00
Speed/torque control
options
0: Speed control
1: Torque control
0
〇
F13.00=0: speed control
The control mode is speed input, and the input is frequency.
F13.00=1: torque control
The input control mode is torque input, and the input is the percentage of the rated torque
current of the motor. This is valid only in the mode of speed sensorless vector control (SVC), i.e.
F00.01=1.
The final control mode is also related to the function terminals “29: torque control
prohibition” and “28: speed control/torque control switching” as detailed below Table 7-18.
Table 7-20 Details of Final Control Mode of Inverter
29: torque control
prohibition
28: speed control/torque
control switching
F13.00
Final control
Valid
*
*
Speed control
Invalid
Valid
0
Torque control
1
Speed control
Invalid
0
Speed control
1
Torque control