![Sinee EM730 Series User Manual Download Page 79](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544079.webp)
User Manual of EM730/EM730E Series Inverter
79
of terminal
start
command
F04.29
Zero speed
check
frequency
0.00 - 5.00
Hz
0.25
●
F04.30
Initial
magnetic
pole search
mode of
synchronous
motor
0: Invalid
1: Mode 1
0
●
F05
V/F control parameter group
F05.00
V/F curve
setting
0: straight line V/F
1: multi-point broken line V/F
2: 1.3-power V/F
3: 1.7-power V/F
4: square V/F
5: VF complete separation mode (Ud = 0, Uq = K * t =
voltage of separation voltage source)
6: VF semi-separation mode (Ud = 0, Uq = K * t = F/Fe *
2 * voltage of separation voltage source)
0
〇
F05.01
Frequency
point F1 of
multi-point
VF
0.00 - F05.03
Hz
0.50
●
F05.02
Voltage point
V1 of
multi-point
VF
0.0
~
100.0 (100.0 = Rated voltage)
%
1.0
●
F05.03
Frequency
point F2 of
multi-point
VF
F05.01
~
F05.05
Hz
2.00
●
F05.04
Voltage point
V2 of
multi-point
VF
0.0-100.0
%
4.0
●
F05.05
Frequency
point F3 of
multi-point
VF
F05.03 to rated frequency of motor (reference frequency)
Hz
5.00
●