User Manual of EM730/EM730E Series Inverter
199
processing of synchronous
motor
1: IF
2: IF in start and VF
in stop
F06.42
Open-loop low-frequency
processing range of
synchronous motor
0.0 - 50.0
%
8.0
〇
F06.43
IF injection current
0.0 - 600.0
%
80.0
〇
The default settings of low frequency optimization options of the synchronous motor are
suitable for most applications. If a larger torque is required at the low frequency, you can enable
the IF mode.
Function
code
Function code name
Parameter
description
Unit
Default
setting
Attribute
F06.46
Speed tracking proportional gain
of synchronous motor
0.00 - 10.00
1.00
〇
F06.47
Speed tracking integral gain of
synchronous motor
0.00 - 10.00
1.00
〇
F06.48
Filtering time constant of speed
tracking of synchronous motor
0.00 - 10.00
ms
0.40
〇
F06.49
Speed tracking control intensity
of synchronous motor
1.0 - 100.0
5.0
〇
F06.50
Speed tracking control threshold
of synchronous motor
0.00 - 10.00
0.20
〇
F06.51
Injection current (Iq) rise time
of synchronous motor
0.010 - 1.000
S
5.0
〇
Tuning parameters for speed tracking of the synchronous motor.
7.8
F07 protection parameter group
Function
code
Function
code name
Parameter description
Unit
Default
setting
Attribute
F07.00
Protection
shield
E20
*
E13
E06
*
E04
E07
E08
0*00*0
00
〇
0: valid protection
1: shielded protection
Bit setting = 0: when the inverter detects the protection corresponding to this bit, it will
stop the output and enter the protection status.
Bit setting = 1: when the inverter detects the protection corresponding to this bit, it will
keep the original status without protection.
This code is subject to bit operation. You only need to set the corresponding bit to 0 or 1.