![Sinee EM730 Series User Manual Download Page 78](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544078.webp)
User Manual of EM730/EM730E Series Inverter
78
F04.14
Acceleration
and
deceleration
mode
0: linear acceleration and deceleration
1: acceleration and deceleration of continuous S curve
2: acceleration and deceleration of intermittent S curve
0
〇
F04.15
Starting time
of S curve in
acceleration
0.00~30.00(F15.13=0)
0.0~300.0(F15.13=1)
0~3000(F15.13=2)
s
1.00
●
F04.16
Ending time
of S curve in
acceleration
0.00~30.00(F15.13=0)
0.0~300.0(F15.13=1)
0~3000(F15.13=2)
s
1.00
●
F04.17
Starting time
of S curve in
deceleration
0.00~30.00(F15.13=0)
0.0~300.0(F15.13=1)
0~3000(F15.13=2)
s
1.00
●
F04.18
Ending time
of S curve in
deceleration
0.00~30.00(F15.13=0)
0.0~300.0(F15.13=1)
0~3000(F15.13=2)
s
1.00
●
F04.19
Stop mode
0: slow down to stop
1: free stop
0
〇
F04.20
Starting
frequency of
DC braking
in stop
0.00Hz to maximum frequency F00.16
Hz
0.00
〇
F04.21
DC braking
current in
stop
0.0
~
100.0 (100.0 = Rated current of motor)
%
50.0%
〇
F04.22
DC braking
time in stop
0.00
~
30.00 0.00: invalid
s
0.00
〇
F04.23
Demagnetiza
tion time for
DC braking
in stop
0.00 - 30.00
s
0.50
〇
F04.24
Flux braking
gain
100-150 (100: no flux braking)
100
〇
F04.26
Start mode
after
protection/fre
e stop
0: start according to F04.00 setting mode
1: start of speed tracking
0
〇
F04.27
Second
confirmation
0: Not required for confirmation
1: to be confirmed
0
〇