![Sinee EM730 Series User Manual Download Page 68](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544068.webp)
User Manual of EM730/EM730E Series Inverter
68
F00.12
Synthetic gain of main and
auxiliary frequency sources
0.0
~
300.0
%
100.0
●
F00.13
Analog adjustment of synthetic
frequency
0: synthetic frequency of main and auxiliary channels
1: AI1 * synthetic frequency of main and auxiliary
channels
2: AI2 * synthetic frequency of main and auxiliary
channels
3: retention
4: retention
5: High frequency pulse (PULSE) * synthetic
frequency of main and auxiliary channels
0
〇
F00.14 Acceleration time 1
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F00.15 Deceleration time 1
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
15.00
●
F00.16 Maximum frequency
1.00~600.00/1.0~3000.0
Hz
50.00
〇
F00.17
Options of upper frequency limit
control
0: set by F00.18
1
:
AI1
2
:
AI2
3: retention
4: retention
5: high frequency pulse input (X5)
6: Communication setting (percentage)
7: Communication setting (direct frequency)
0
〇
F00.18 Upper frequency limit
Lower frequency limit F00.19 to maximum frequency
F00.16
Hz
50.00
●
F00.19 Lower frequency limit
0.00 to upper frequency limit F00.18
Hz
0.00
●
F00.20 Running direction
0: consistent direction
1: opposite direction
0
●
F00.21 Reverse control
0: Allow forward/reverse running
1: Prohibit reversing
0
〇
F00.22
Duration of forward and reverse
dead zone
0.00
~
650.00
s
0.00
●
F00.23 Carrier frequency
1.0-16.0 (rated power of the inverter: 0.75-4.00kW)
1.0-10.0 (rated power of the inverter: 5.50-7.50kW)
1.0 - 8.0 (rated power of inverter 11.00 - 45.00kW)
1.0 - 4.0 (rated power of inverter 55.00 - 90.00kW)
1.0-3.0 (rated power of inverter: 110.00 and above)
kHz
4.0 (0.75
and
below)
/2.0
●
F00.24
Automatic adjustment of carrier
frequency
0: Invalid
1: valid 1
2: Valid 2
1
〇