User Manual of EM730/EM730E Series Inverter
188
Output voltage
(%)
Rated voltage
of motor
V3
V2
V1
F1
F2
F3
Rated frequency
of motor
Output frequency
(
%
)
Fig. 7-19 Schematic Diagram of Multi-point Polyline V/F Curve
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F05.07
Voltage source of
VF separation mode
0: digital setting of VF
separation voltage
1: AI1
2: AI2
3: retention
4: High-frequency pulse (X5)
5
:
PID
6: Communication setting
Note: 100% is the rated voltage
of the motor.
0
〇
F05.08
Digital setting of VF
separation voltage
0.0 to 100.0 (100.0=Rated
voltage of motor)
%
0.0
●
VF separation is usally applied in induction heating, inverter power supply, torque motor
control, etc.
When VF separation control is selected, the output voltage can be set by the function code
F05.08 or according to the analog, high-speed pulse, PID or communication settings. For
non-digital settings, 100% of each setting corresponds to the rated voltage of the motor. When
the percentage set by the analog output is negative, the set absolute value will be taken as the
valid set value.
F05.07=0: digital setting of VF separation voltage (F05.08)
The VF separation output voltage depends on the digital setting of VF separation voltage
(F05.08).
F05.07=1:AI1