User Manual of EM730/EM730E Series Inverter
210
four running modes in total, as detailed in Table 7-13.
Table 7-13 Details of PLC Running Mode
F08.15
Description
0
The inverter will be stopped after running in the last segment.
1
The inverter will run cyclically and be stopped after the set cycles. The number
of cycles depends on the function code F08.16.
2
The inverter will run cyclically and keep the speed of the last segment after
running in the last segment, until a stop command is received. The number of
cycles depends on the function code F08.16.
3
The inverter will continue cyclic operation until a stop command is received.
★
The last segment refers to the segment that is not set to 0, judged from the running
time (F08.48) of the 15
th
segment toward the 1
st
segment.
T1
T2
T4
T5
T12
T13
1
2
4
5
12
13
Output frequency (Hz)
Time (s)
Fig. 7-26 Schematic Diagram of Simple PLC Operation
Fig. 7-26 shows the operation diagram in the running mode “0: stop after a single run”.
Since the running time of the 3
rd
segment is set to 0 (F08.24=0.0), the 3
rd
segment will not be
put into actual operation. The running time of the 14
th
and 15
th
segments is set to 0 (F08.46=0.0,
F08.48=0.0), so the last segment is the 13
th
segment, and the inverter will be stopped after
running in the 13
th
segment.
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F08.17
Simple PLC
memory options
Ones place:
Stop memory
options
0: no memory (from the first
segment)
00
●