User Manual of EM730/EM730E Series Inverter
253
mode (Ud = 0, Uq = K * t
= F/Fe * 2 * voltage of
separation voltage source)
F14.81
Multi-point VF
frequency F1 of motor
2
0.00 - F14.83
Hz
0.50
●
F14.82
Multi-point VF voltage
V1 of motor 2
0.0
~
100.0 (100.0 = Rated
voltage)
%
1.0
●
F14.83
Multi-point VF
frequency F2 of motor
2
F14.81 - F14.85
Hz
2.00
●
F14.84
Multi-point VF voltage
V2 of motor 2
0.0-100.0
%
4.0
●
F14.85
Multi-point VF
frequency F3 of motor
2
F14.83 to rated frequency
of motor (reference
frequency)
Hz
5.00
●
F14.86
Multi-point VF voltage
V3 of motor 2
0.0-100.0
%
10.0
●
See F05.00 to F05.06
Function
code
Function code name
Parameter description Unit
Default
setting
Attribute
F14.87
Stop mode of motor 2
0: Slow down to stop
1: Free stop
0
〇
See F04.19
7.16
Auxiliary Function Parameter Group of F15 Group
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F15.00 Jog frequency
0.00 to maximum frequency
F00.16
Hz
5.00
●
F15.01
Jog acceleration
time
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
5.00
●
F15.02
Jog deceleration
time
0.00 - 650.00 (F15.13=0)
0.0 - 6500.0 (F15.13=1)
0 - 65000 (F15.13=2)
s
5.00
●
As shown in Fig. 7-32, when the jog running command (FJOG/RJOG) is valid, the inverter
will start running at the set frequency of F15.00; and when the jog running command is invalid,
the inverter will be stopped according to the stop mode.