User Manual of EM730/EM730E Series Inverter
203
voltage is higher than the instantaneous stop/non-stop recovery voltage (F07.09), the inverter
will not slow down. When the cumulative time reaches the judgement time for instantaneous
stop/non-stop recovery voltage (F07.10), the inverter will start to acceleration, and the frequency
will gradually return to the set value.
When the ones place of the instantaneous stop/non-stop option of F07.06 bus voltage
control is set to “2: Slow down to stop”, the action is similar to that of the option 1. When the
bus voltage reaches the instantaneous stop/non-stop action voltage, the speed set based on the
instantaneous stop/non-stop slowdown time (F07.30) will constantly decrease to 0, regardless of
voltage recovery.
DC bus voltage
Time
Output frequency
Instantaneous stop/no-
stop recovery voltage
Instantaneous stop/no-
stop operating voltage
Judgment time for
voltage recovery
Fig. 7-24 Schematic Diagram of Instantaneous Stop/Non-stop Deceleration Function
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F07.11
Current limit
control
0: Invalid
1: limit mode 1
2: limit mode 2
2
〇
F07.12 Current limit level
20.0-180.0 (100% = rated current
of inverter)
%
150.0
●
F07.11=0: invalid
The current limit does not work.