User Manual of EM730/EM730E Series Inverter
189
F05.07=2:AI2
F05.07=4: High-frequency pulse (X5)
The VF separation output voltage depends on AI/HDI (percentage) * F05.08 (digital setting
of VF separation voltage).
For the details of AI1-AI2 and X5, refer to the F00.04 description. They have the same
meaning. 100.00% is the percentage to the set value of F05.08 (digital setting of VF separation
voltage).
F05.07=5: process PID
The VF separation output voltage depends on the process PID function output, as described
in 7.10.
F05.07=6: communication setting
The VF separation output voltage depends on the communication.
If the master-slave communication (F10.05=1) is enabled and the inverter works as the
slave (F10.06=0), the VF separation output voltage is “700FH (master-slave
communication setting) * F01.02 or others (rated voltage of the motor) * F10.08
(slave receiving proportional coefficient)”. The 700FH data range is 0.00% to
100.00%, as detailed in Table 12-31.
For general communication (F10.05=0), the VF separation output voltage is “7006H
(voltage setting of the VF separation mode) * F05.08 (digital setting of the VF
separation voltage)”, and the 7006H data range is 0.00% to 100.00%, as detailed in
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F05.09
Rise time of VF
separation voltage
0.00 - 60.00
s
2.00
●
The rise time of VF separation voltage refers to the time for the output voltage to increase
from 0 to the rated voltage of the motor.