User Manual of EM730/EM730E Series Inverter
62
(c) Wiring diagram of three-line control (F00.03=3)
(d) Forward/reverse running logic
(F04.19=0, F00.03=3)
Fig. 5-3 Three-line Control
The three-line control logic of the EM730/EM730E series inverter is consistent with the
conventional electrical control. The keys and knob switches should be used correctly as
shown in the schematic diagram. Otherwise, operation errors may be caused.
5.6
Common Process Parameters of Inverter
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F00.01 Drive control mode of motor 1
0: V/F control (VVF)
1: Speed sensorless vector
control (SVC)
0
〇
F00.04
Options of main frequency
source A
0: digital frequency setting
F00.07
1
:
AI1
2
:
AI2
5: high frequency pulse input
(X5)
6: Percentage setting of main
frequency communication
7: Direct setting of main
frequency communication
8: digital potentiometer
setting
0
〇
F00.07 Digital frequency setting
0.00 to maximum frequency
F00.16
Hz
0.00
●
F00.14 Acceleration time 1
0.00
~
650.00
(
F15.13=0
)
s
15.00
●
F00.15 Deceleration time 1
0.00
~
650.00
(
F15.13=0
)
s
15.00
●
F00.16 Maximum frequency
1.00
~
600.00
Hz
50.00
〇
F00.18 Upper frequency limit
Lower frequency limit F00.19
to maximum frequency
F00.16
Hz
50.00
●
F00.19 Lower frequency limit
0.00 to upper frequency limit
F00.18
Hz
0.00
●
F00.21 Reverse control
0: Allow forward/reverse
running 1: Prohibit
reversing
0
〇
Note: Common process parameters may also include the input and output terminal function