![Sinee EM730 Series User Manual Download Page 329](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544329.webp)
User Manual of EM730/EM730E Series Inverter
329
Others to 00FFH
Reserved
7001H
Communication
percentage setting
of main channel
frequency A
-100.00% to 100.00% (100% = maximum
frequency)
7002H
Communication
percentage setting
of auxiliary
channel frequency
B
-100.00% to 100.00% (100% = maximum
frequency)
7003H
Torque
communication
setting
-200.00% to 200.00% (100% = digital
torque setting)
7004H
Communication
setting of process
PID setting
-100.00% - 100.00%
7005H
Communication
setting of process
PID feedback
-100.00% - 100.00%
7006H
Voltage setting of
VF separation
mode
0.00% to 100.00% (digital setting reference)
7007H to
7009H
Reserved
700AH
Communication
percentage setting
of upper frequency
limit
0.00% to 200.00% (digital setting reference)
700BH
Communication
percentage setting
of upper frequency
limit of torque
control
0.00% to 200.00% (digital setting reference)
700CH
Linear speed input for
inertia compensation
0.00% to 100.00% (digital setting reference)
700DH to
700EH
Reserved
700FH
Master-slave
communication
setting
-100.00%to 100.00% (maximum reference)
7010H to
7013H
Reserved
7014H
External
Protection input of external device