User Manual of EM730/EM730E Series Inverter
323
Response PDU
Function code
1 byte
0x42
Starting Address
2 bytes
0x0000 - 0xFFFF
Number of
registers
2 bytes
1 - 16
Error PDU
Error code
1 byte
0xC2
Exception code
1 byte
Below is an example of a request to set the acceleration time 1 (F00.14) to 5.00 and
deceleration time 1 (F00.15) to 6.00:
Request
Respond
Domain name
(0x)
Domain name
(normal)
(0x)
Domain name
(abnormal)
(0x)
Function
42
Function
42
Function
C2
Starting address Hi
00
Starting address
Hi
00
Exception
code
03
Starting address Lo
0E
Starting address
Lo
0E
Number (Hi) of registers
00
Number (Hi) of
registers
00
Number (Lo) of registers
02
Number (Lo) of
registers
02
Number of bytes
04
Register value Hi
(F00.14)
01
Register value Lo
(F00.14)
F4
Register value Hi
(F00.15)
02
Register value Lo
(F00.15)
58
★
This function code cannot be used to change the parameters of the attribute “○” (it
cannot be changed during operation). That is, only the parameters of the attribute “●”
(it can be changed during operation) can be changed. Otherwise, the error code 1 will
be returned.