![Sinee EM730 Series User Manual Download Page 259](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544259.webp)
User Manual of EM730/EM730E Series Inverter
259
Time
Output frequency
Set frequency
Time
Output terminal
Valid
0
0
Invalid
Invalid
Set frequency -
width
Set fre
width
V
al
id
Invalid
Fig. 7-36 Schematic Diagram of FAR Detection
As shown in Fig. 7-36, when the multi-function output terminal or relay output is set to “2:
up to output frequency (FAR)”, and the absolute value of the difference between the |output
frequency| and |given frequency| is less than or equal to the set value of FAR detection width
(F15.20) during inverter operation, the corresponding function terminal will output the active
level. Otherwise, this terminal will output the inactive level.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F15.21
Output frequency
detection FDT1
0.00 to maximum
frequency F00.16
Hz
30.00
〇
F15.22 FDT1 hysteresis
-(Fmax-F15.21)
~
F15.21
Hz
2.00
〇
F15.23
Output frequency
detection FDT2
0.00 to maximum
frequency F00.16
Hz
20.00
〇
F15.24 FDT2 hysteresis
-(Fmax-F15.23)
~
F15.23
Hz
2.00
〇