User Manual of EM730/EM730E Series Inverter
168
be valid. When the inverter is not suitable for running, the
current output will be invalid.
9
Reach the upper
frequency limit
When the inverter is in the JOG or slave running status, the
output frequency (F18.00) is greater than or equal to the
upper frequency limit (F00.17||F00.18), and the set
frequency (F18.01) is greater than or equal to the upper
frequency limit (F00.17||F00.18), the current output will be
valid. Otherwise, the current output will be invalid.
10
Reach the lower
frequency limit
When the inverter is in the JOG or slave running status, the
output frequency (F18.00) is less than or equal to the lower
frequency limit (F00.19), and the set frequency (F18.01) is
less than or equal to the lower frequency limit (F00.19), the
current output will be valid. Otherwise, the current output
will be invalid.
11
Valid current limit
When the output current (F18.06) is greater than or equal to
the current limit (F07.12), the current output will be valid;
when the output current (F18.06) is less than or equal to the
current limit (F07.12) -5.0%, the current output will be
invalid; and when the output current is an intermediate
value, the current output will remain unchanged.
12
Valid overvoltage
stall
When the output voltage (F18.07) is greater than or equal
to the voltage of overvoltage stall control (F07.07), the
current output will be valid; when the output voltage
(F18.07) is less than or equal to the voltage of overvoltage
stall control (F07.07) minus 10V, the current output will be
invalid; and when the output voltage is an intermediate
value, the current output will remain unchanged.
13
Complete simple
PLC cycle
When the simple PLC is in the mode of stop after a single
operation (F18.15=0), it will be stopped after one operation
and the current output will be valid; when the simple PLC
is in the mode of stop after a limited number of operations
(F18.15=1), it will be stopped after the operations set by
F08.16, and the current output will be valid; otherwise (e.g.
further running, simple PLC status resetting), the current
output will be invalid.
14
Reach the set count
value
When the input pulse count value (F18.34) is greater than
or equal to the set count value (F16.03), the current output
will be valid; otherwise, the output will be invalid. See the
description of function codes F16.03 to F16.04.