User Manual of EM730/EM730E Series Inverter
139
or negative. That is, the result of the forward 20.00Hz and reverse 40.00Hz is reverse 40.00Hz.
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F00.09
Reference options of
auxiliary frequency
source B in main and
auxiliary operation
0: relative to he maximum
frequency
1: Relative to main frequency
source A
0
〇
During the main and auxiliary operations, the range of the auxiliary frequency source B
depends on the selected object, maximum frequency by default. If selected relative to the main
frequency source A (F00.09=1), the range of the auxiliary frequency source B will change along
with that of the main frequency source A (according to the maximum frequency by default).
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F00.10
Gain of main frequency
source
0.0
~
300.0
%
100.0
●
F00.11
Gain of auxiliary
frequency source
0.0
~
300.0
%
100.0
●
F00.12
Synthetic gain of main
and auxiliary frequency
sources
0.0
~
300.0
%
100.0
●
F00.13
Analog adjustment of
synthetic frequency
0: synthetic frequency of main
and auxiliary channels
1: AI1 * synthetic frequency of
main and auxiliary channels
2: AI2 * synthetic frequency of
main and auxiliary channels
3: retention
4: retention
5: High frequency pulse
(PULSE) * synthetic frequency
of main and auxiliary channels
0
〇
Such parameters are mainly used to adjust the gain of each setting source, as shown in