![Sinee EM730 Series User Manual Download Page 320](http://html1.mh-extra.com/html/sinee/em730-series/em730-series_user-manual_1280544320.webp)
User Manual of EM730/EM730E Series Inverter
320
The register data in the response message is divided into two bytes in each register. The
first byte of each register includes high-order bits and the second byte includes low-order bits.
Request PDU
Function code
1 byte
0x03
Starting Address
2 bytes
0x0000 - 0xFFFF
Number of registers
2 bytes
1 - 16
Response PDU
Function code
1 byte
0x03
Number of bytes
1 byte
2×N*
Register value
N*×2 bytes
N* = number of registers
Error PDU
Error code
1 byte
0x83
Exception code
1 byte
01, 02, 03 or 04
Below is an example of a request to read the registers F19.00 to F19.05 (relevant
information about the last protection):
Request
Respond
Domain name
(0x)
Domain name (normal)
(0x) Domain
name
(abnormal)
(0x)
Function code
03
Function code
03
Function
83
Starting address
Hi
13
Number of bytes
0C
Exception code
03
(example,
the same
below)
Starting address
Lo
00
Register value Hi
(F19.00)
00
Number (Hi) of
registers
00
Register value Lo
(F19.00)
11
Number (Lo) of
registers
06
Register value Hi
(F19.01)
00
Register value Lo
(F19.01)
00
Register value Hi
(F19.02)
00
Register value Lo
(F19.02)
00