3-11
Section 3
CQO:1010PVXFM-3
Put mounting strap around transducer and tighten as in Step 5. Sight along spacer bar to ensure axial
alignment to the pipe. Adjust if necessary and do not overtighten. Ensure that the transducers do not
move while tightening.
7. Connect the transducer cable, ensuring that you have observed the upstream/downstream orienta-
tion in respect to the cable and the input jack on the flow computer. If this is a dual-channel unit, make
sure you are connecting the cables to the correct channel’s input jacks. Repeat this procedure for the
number index transducer.
8. Return to the menu, and press <ENT> to finish the transducer install routine.
3.3.8 DIRECT MODE - MOUNTING FRAMES, SPACER BAR AND SPACING GUIDES
The combination of mounting frames, spacer bar and spacing guides is the recommended way to mount
Direct Mode transducers. The mounting frame establishes the axial alignment of the transducers, and
allows you to remove and replace either transducer while preserving their exact mounting location.
For Direct Mode mounting, you will use a spacer bar to establish the distance between transducers and
a spacing guide to easily locate the transducers at the nine o’clock and three o’clock positions. Should the
distance between transducers be beyond the span of a spacer bar, a measuring tape can be used. The
Mylar spacing guide comes in various lengths and widths to accommodate most pipe sizes (see list
below).
I
NSTALLATION - DIRECT MODE WITH TRANSDUCERS, MOUNTING FRAMES,
SPACER BAR (Not Shown) AND SPACING GUIDE
Ltn
Transducer
Clamping
Screw
Mounting
Frame
Mounting
Strap
Ltn
Reference
Notch
Mounting Strap
Adjusting Screw
Spacing Guide P/N
Size
1012-145-1A
2" x 26" (50.8 x 660.4 mm)
1012-145-1
2" x 45" (50.8 x 1143.0 mm)
1012-145-2
4" x 81" (101.6 x 2057.4 mm)
1012-145-3
4" x 155" (101.6 x 3937.0 mm)
Summary of Contents for SITRANS FUH1010PVDX
Page 2: ......
Page 4: ......
Page 8: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 32: ......
Page 184: ......
Page 204: ......
Page 206: ......
Page 208: ......
Page 216: ......
Page 219: ...21614 C 1010X 7 CAUTION ...
Page 222: ...STANDARD UPRIGHT INSTALLATION 21614 C 1010X 8 ...
Page 223: ...21614 C 1010DX 7 CAUTION ...
Page 227: ...21614 C 1010DX 8 STANDARD UPRIGHT INSTALLATION ...
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ...1011HNFS 7 21614 C ...
Page 235: ...1011HNFS 7 C 21614 ...
Page 237: ......
Page 241: ...1011NFPS 7 C 21614 REFLECT MODE OPERATION DIRECT MODE OPERATION AUXILIARY VIEW ...
Page 242: ...1011NFPS 8 21614 C ...
Page 243: ......
Page 249: ......
Page 250: ......
Page 251: ...1012TB 8 INSTALLATION OUTLINE 1011 SERIES TEST BLOCK 21614 C ...
Page 254: ...1012TN 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TN SERIES 21614 C MOUNTING TRACK ...
Page 257: ...1012TNH 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TNH SERIES 21614 C MOUNTING TRACK ...
Page 258: ...1012F DB 7 21614 C ...
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ...21614 C OUTLINE DIMENSIONS WELD SEAL TYPE 1013WS 8 ENCLOSURES ...
Page 263: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 267: ......
Page 269: ...21614 C TEMPERATURE SENSOR DEDICATED NEMA 4 OUTLINE DIMENSIONS 991TN 8 5 4 3 2 1 ...
Page 270: ......
Page 271: ......
Page 273: ......
Page 274: ......
Page 275: ......
Page 276: ......
Page 286: ......
Page 304: ......
Page 307: ......