5-62
CQO:1010PVXFM-3
Section 5
Assigning Io Output Functions (see paragraph 5.10.6)
The Io analog output is a loop-powered (or externally powered), isolated 4-20mA DC signal that varies
linearly in relation to a selected data function.
To assign a function for the current output:
From Analog Out Setup, press twice to access the Io option list.
Move the cursor to the desired data function by pressing
To store selection press
Assigning Pgen Output Functions (Only availabe in single channel Models - see para-
graph 5.10.6)
The Pgen analog output is a opto-coupled pulse rate signal whose configuration is detailed in Installation
Drawing 1010DX-7. It varies linearly from 0-5000 Hz in relation to a selected data function.
To assign a function to the Pgen output:
To access the Pgen option list press
Move the cursor to the desired data function by pressing
To store selection press
ENT
ENT
5.9.1 ANALOG OUTPUT SETUP
The FUH1010PVX provides current, voltage and pulse-rate analog outputs. Analog Output Setup allows
you to assign data functions for these signals. The flow display computer’s terminal strip contains the
analog output terminals.
Io
(Isolated current)
4 to 20 mA varies in proportion to an assigned data function.
Pgen
(TTL logic)
0 to 5000 Hz varies in proportion to an assigned data function.
Digital Pgen
User selective pulses per unit flow (Custody Transfer units only
System FUH1010PVX Analog Outputs
NOTE: For Multi-Path flowmeters: “1” = Path 1, “2” = Path 2, “3” = Path 3, “4” = Path
4 and “S” represents the system or average channel. These characters appear to
the left of the option list parameter.
S LiquIdent m/s
System sonic velocity compensated for temperature.
S Viscosity
System liquid viscosity.
S T1
Current liquid temperature.
S Vfo
System spanned volumetric flow (unsigned).
S Vfo2
Additional system spanned volumetric flow (unsigned).
S Vfab
System spanned and signed absolute flow.
S Vs
System liquid sonic velocity.
S Valc
System signal amplitude.
S Vaer
System aeration number.
Iin1, Iin2
Represents a re-transmit of the analog input signals (e.g.,
Pressure and Temp inputs can be transmitted on the 4/20 mA
output).
Analog Out Setup Data Categories
Summary of Contents for SITRANS FUH1010PVDX
Page 2: ......
Page 4: ......
Page 8: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 32: ......
Page 184: ......
Page 204: ......
Page 206: ......
Page 208: ......
Page 216: ......
Page 219: ...21614 C 1010X 7 CAUTION ...
Page 222: ...STANDARD UPRIGHT INSTALLATION 21614 C 1010X 8 ...
Page 223: ...21614 C 1010DX 7 CAUTION ...
Page 227: ...21614 C 1010DX 8 STANDARD UPRIGHT INSTALLATION ...
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ...1011HNFS 7 21614 C ...
Page 235: ...1011HNFS 7 C 21614 ...
Page 237: ......
Page 241: ...1011NFPS 7 C 21614 REFLECT MODE OPERATION DIRECT MODE OPERATION AUXILIARY VIEW ...
Page 242: ...1011NFPS 8 21614 C ...
Page 243: ......
Page 249: ......
Page 250: ......
Page 251: ...1012TB 8 INSTALLATION OUTLINE 1011 SERIES TEST BLOCK 21614 C ...
Page 254: ...1012TN 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TN SERIES 21614 C MOUNTING TRACK ...
Page 257: ...1012TNH 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TNH SERIES 21614 C MOUNTING TRACK ...
Page 258: ...1012F DB 7 21614 C ...
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ...21614 C OUTLINE DIMENSIONS WELD SEAL TYPE 1013WS 8 ENCLOSURES ...
Page 263: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 267: ......
Page 269: ...21614 C TEMPERATURE SENSOR DEDICATED NEMA 4 OUTLINE DIMENSIONS 991TN 8 5 4 3 2 1 ...
Page 270: ......
Page 271: ......
Page 273: ......
Page 274: ......
Page 275: ......
Page 276: ......
Page 286: ......
Page 304: ......
Page 307: ......