5-38
CQO:1010PVXFM-3
Section 5
5.5.3 MEMORY/FAULT SET
Certain situations (e.g., an empty pipe or excessive aeration) will interrupt data production. Use Memory/
Fault Set to select the meter response to such an interruption. The Fault setting (default) will zero the flow
rate output and declare an alarm on a flow display screen, Datalogger report and an assigned relay
output.
For some applications, occasional temporary Fault conditions may be a normal part of the process and
would not require an alarm response. The system offers a Memory operating mode to support such an
application. Memory Mode suspends the system’s Fault response by preventing the flow outputs from
dropping to zero for the interval specified in the [Memory Delay] menu cell. During the Memory duration,
the meter will maintain the last valid flow reading measured before the onset of the fault condition. The
default Memory Delay is 60 seconds. You may select any duration from 3 to 604,800 seconds (one
week).
To select Memory mode:
To access the [Memory/Fault] option list press
Move the cursor down to [Memory] by pressing
To make selection press
This moves the highlight to [Memory Delay <sec>].
Memory Delay <sec>
Selecting [Memory] activates the suppressed [Memory Delay] menu cell. It allows you to specify the
number of seconds that the meter maintains its last valid flow reading. When the memory delay expires,
it triggers the fault alarm response described previously.
To specify the Memory Delay:
To enable numeric entry press
Use PC numeric keys or Magnetic Wand to enter the delay in seconds.
To register the new value press
ENT
ENT
Summary of Contents for SITRANS FUH1010PVDX
Page 2: ......
Page 4: ......
Page 8: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 32: ......
Page 184: ......
Page 204: ......
Page 206: ......
Page 208: ......
Page 216: ......
Page 219: ...21614 C 1010X 7 CAUTION ...
Page 222: ...STANDARD UPRIGHT INSTALLATION 21614 C 1010X 8 ...
Page 223: ...21614 C 1010DX 7 CAUTION ...
Page 227: ...21614 C 1010DX 8 STANDARD UPRIGHT INSTALLATION ...
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ...1011HNFS 7 21614 C ...
Page 235: ...1011HNFS 7 C 21614 ...
Page 237: ......
Page 241: ...1011NFPS 7 C 21614 REFLECT MODE OPERATION DIRECT MODE OPERATION AUXILIARY VIEW ...
Page 242: ...1011NFPS 8 21614 C ...
Page 243: ......
Page 249: ......
Page 250: ......
Page 251: ...1012TB 8 INSTALLATION OUTLINE 1011 SERIES TEST BLOCK 21614 C ...
Page 254: ...1012TN 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TN SERIES 21614 C MOUNTING TRACK ...
Page 257: ...1012TNH 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TNH SERIES 21614 C MOUNTING TRACK ...
Page 258: ...1012F DB 7 21614 C ...
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ...21614 C OUTLINE DIMENSIONS WELD SEAL TYPE 1013WS 8 ENCLOSURES ...
Page 263: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 267: ......
Page 269: ...21614 C TEMPERATURE SENSOR DEDICATED NEMA 4 OUTLINE DIMENSIONS 991TN 8 5 4 3 2 1 ...
Page 270: ......
Page 271: ......
Page 273: ......
Page 274: ......
Page 275: ......
Page 276: ......
Page 286: ......
Page 304: ......
Page 307: ......