5-18
CQO:1010PVXFM-3
Section 5
Setting the LiquIdent Index
A Liquid Class must have an associated LiquIdent Index Scale. The FUH1010PVX uses this scale to
compensate its outputs for variations in liquid type, specific gravity, and viscosity. The LiquIdent Index
Scale enables the following:
Reynolds number compensation over the entire temperature range.
Positive liquid identification.
A LiquIdent Index is the sonic velocity for the liquid at the Base Temperature, generally 60ºF (15ºC).
When a LiquIdent Index is entered for a particular liquid within the Liquid Class, the liquid’s specific gravity
and its viscosity must also be entered at the LiquIdent Index.
To create a LiquIdent Index Scale for the Liquid Class, a minimum of two LiquIdent Indices are required to
be entered. If desired, up to thirty-two LiquIdent Indices can be entered. However, the computer only
needs two to establish a scale of all the possible LiquIdent™ indices for the Liquid Class. If a LiquIdent
beyond the limits of the table is sensed, the instrument uses the last valid values creating a “clipped”
table. The instrument does not extrapolate output variables.
After the computer interpolates the LiquIdent Index Scale, its projections can be checked by entering a
meaningful LiquIdent Index and examining the reported specific gravity and viscosity values. The scale
can be fine-tuned by manually adjusting the factors at up to thirty-two points.
To enter the LiquIdent Index:
From the [Liquid Table] menu cell, press to scroll down to [LiquIdent Index].
Press to enable numeric entry.
Use the keypad numeric keys to enter the desired LiquIdent Index.
To enter the LiquIdent Index press .
ENT
Calculate the average of all the Pressure Slope Factors within the Liquid Class.
To enter the Pressure Slope Factor:
From the [Liquid Table] menu cell, press to scroll down to
Pressure Slope
.
Press to enable numeric entry.
Use the keypad numeric keys to enter the desired Pressure Slope Factor.
To enter the Pressure Slope Factor press .
ENT
Summary of Contents for SITRANS FUH1010PVDX
Page 2: ......
Page 4: ......
Page 8: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 32: ......
Page 184: ......
Page 204: ......
Page 206: ......
Page 208: ......
Page 216: ......
Page 219: ...21614 C 1010X 7 CAUTION ...
Page 222: ...STANDARD UPRIGHT INSTALLATION 21614 C 1010X 8 ...
Page 223: ...21614 C 1010DX 7 CAUTION ...
Page 227: ...21614 C 1010DX 8 STANDARD UPRIGHT INSTALLATION ...
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ...1011HNFS 7 21614 C ...
Page 235: ...1011HNFS 7 C 21614 ...
Page 237: ......
Page 241: ...1011NFPS 7 C 21614 REFLECT MODE OPERATION DIRECT MODE OPERATION AUXILIARY VIEW ...
Page 242: ...1011NFPS 8 21614 C ...
Page 243: ......
Page 249: ......
Page 250: ......
Page 251: ...1012TB 8 INSTALLATION OUTLINE 1011 SERIES TEST BLOCK 21614 C ...
Page 254: ...1012TN 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TN SERIES 21614 C MOUNTING TRACK ...
Page 257: ...1012TNH 8 OUTLINE DIMENSIONS REFLECT MODE DIRECT MODE 1012TNH SERIES 21614 C MOUNTING TRACK ...
Page 258: ...1012F DB 7 21614 C ...
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ...21614 C OUTLINE DIMENSIONS WELD SEAL TYPE 1013WS 8 ENCLOSURES ...
Page 263: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 267: ......
Page 269: ...21614 C TEMPERATURE SENSOR DEDICATED NEMA 4 OUTLINE DIMENSIONS 991TN 8 5 4 3 2 1 ...
Page 270: ......
Page 271: ......
Page 273: ......
Page 274: ......
Page 275: ......
Page 276: ......
Page 286: ......
Page 304: ......
Page 307: ......