Description:
Sets the pulse width for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 1 (square-wave).
Description:
Sets the bandwidth for the signal to be generated for the function generator.
Dependency:
Only effective when p4820 = 4 (PRBS).
Refer to: p4830
Description:
Sets the amplitude for the signal to be generated for the function generator.
Dependency:
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
Description:
Sets the second amplitude for the signal to be generated for the function generator.
Dependency:
Only effective for p4820 = 2 (staircase).
Units are dependent on p4810.
If p4810 = 1, 2, 4: The amplitude is referred to p2002 (reference current).
If p4810 = 3, 5: The amplitude is referred to p2000 (reference speed).
p4822
Function generator pulse width / FG pulse width
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0.00 [ms]
60000.00 [ms]
500.00 [ms]
p4823
Function generator bandwidth / FG bandwidth
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
0.0025 [Hz]
16000.0000 [Hz]
4000.0000 [Hz]
p4824
Function generator amplitude / FG amplitude
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
-1600.00 [%]
1600.00 [%]
5.00 [%]
p4825
Function generator 2nd amplitude / FG 2nd amplitude
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
-
P-Group:
Trace and function generator
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
0
Min Max
Factory
setting
-1600.00 [%]
1600.00 [%]
7.00 [%]