SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
203
2 Parameters
2.2 List of parameters
Re bit 09:
When evaluating the encoder signals (track signals, zero marks, absolute values, ...) an illegal signal state was
detected. Check the encoder / state of the encoder signals. Observe the maximum frequencies.
Re bit 10:
The internal communication between the SINAMICS components is faulted or interrupted. Check the DRIVE-CLiQ
wiring. Ensure an EMC-compliant design. Observe the maximum permissible quantity structure / clock cycles.
Re bit 11:
The infeed is faulted or has failed. Check the infeed and the surroundings (line supply, filter, reactors, fuses, ...).
Check the closed-loop infeed control.
Re bit 15:
Group fault. Determine the precise cause of the fault using the commissioning tool.
Description:
Displays the global status word for messages.
The appropriate bit is set if at least one message is present at the drive objects.
Note:
The status bits are displayed with delay.
Description:
Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
Description:
Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r3114.9...11
CO/BO: Messages status word global / Msg ZSW global
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
-
Calculated:
-
Access level:
2
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Displays, signals
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
09
Group alarm present
Yes
No
8065
10
Group fault present
Yes
No
8060
11
Safety group message present
Yes
No
-
r3115[0...63]
Fault drive object initiating / F DO initiating
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
-
Func. diagram:
-
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
r3115[0...63]
Fault drive object initiating / F DO initiating
TM150, TM15DI_DO,
TM31
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Integer32
Dyn. index:
-
Func. diagram:
8050, 8060
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......