2 Parameters
2.2 List of parameters
SINAMICS DCM
504
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the signal source for enabling analog input 1 (X177.27/28) on the CUD.
Note:
1 signal:
Analog input is enabled
0 signal:
Analog input is disabled (value = 0%)
Description:
Sets the setpoint for the simulation of analog input 1 (X177.27/28) on the CUD.
Dependency:
Refer to: p50719
Note:
Simulation is selected using p50719 = 1.
Description:
Setting to select the simulation of analog input 1 (X177.27/28) on the CUD.
Value:
0:
Simulation deactivated
1:
Simulation activated
Dependency:
Refer to: p50717
Note:
The setpoint for the simulation is set in p50717.
Description:
Sets the scaling for analog input 2 (X177.29/30) on the CUD.
The value indicates the percentage value for the mapping of an input voltage of 10 V at the analog input.
Example:
p50721 = 90%
--> 10 V is scaled to 90 %
--> 5 V corresponds to 45 %
Note:
AI: Analog Input
p50716
BI: CUD analog input 1 signal source for enable / CUD AI 1 ena sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
2080
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p50717
CUD analog input 1 simulation setpoint / CUD AI 1 sim setp
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2080
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-130.0 [%]
130.0 [%]
0.0 [%]
p50719
CUD analog input 1 simulation selection / CUD AI 1 sim sel
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2080
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50721[0...n]
CUD analog input 2 scaling / CUD AI 2 scal
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
2080
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-1000.0 [%]
1000.0 [%]
100.0 [%]