2 Parameters
2.2 List of parameters
SINAMICS DCM
500
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the type for analog input 0 (X177.25/26) on the CUD.
Value:
0:
Bipolar voltage input (-10 V ... +10 V)
1:
Bipolar current input (-20 mA to +20 mA)
2:
Unipolar current input monitored (+4 mA to +20 mA)
Note:
AI: Analog Input
Description:
Sets the scaling for analog input 0 (X177.25/26) on the CUD.
The value indicates the percentage value for the mapping of an input voltage of 10 V or an input current of 20 mA at
the analog input.
Example:
p50701 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Description:
Sets the offset for analog input 0 (X177.25/26) on the CUD.
Description:
Sets the signal processing mode for analog input 0 (X177.25/26) on the CUD.
Value:
0:
Signal not controlled
1:
Signal absolute value generation
2:
Signal inverted
3:
Signal absolute value generation inverted
p50700
CUD analog input 0 type / CUD AI 0 type
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
0
p50701[0...n]
CUD analog input 0 scaling / CUD AI 0 scal
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-1000.0 [%]
1000.0 [%]
100.0 [%]
p50702
CUD analog input 0 offset / CUD AI 0 offs
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
p50703
CUD analog input 0 signal processing / CUD AI 0 sig proc
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
0
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......