2 Parameters
2.2 List of parameters
SINAMICS DCM
174
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2114, r2122, r2123, r2124, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2114, r2122, r2123, r2124, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8065
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
TM150, TM15DI_DO,
TM31
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dyn. index:
-
Func. diagram:
8050, 8065
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
p2126[0...19]
Change acknowledge mode fault number / Chng ackn F_no
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
8075
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0
p2126[0...19]
Change acknowledge mode fault number / Chng ackn F_no
TM150, TM15DI_DO,
TM31
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
8050, 8075
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 65535
0