2 Parameters
2.2 List of parameters
SINAMICS DCM
502
List Manual (LH8), 02/2015, 6RX1800-0ED76
Value:
0:
No synchronized analog inputs
1:
6 synchronized analog inputs on left-hand CUD
2:
6 synchronized analog inputs on right-hand CUD
3:
6 synchronized analog inputs on left-hand and right-hand CUD
Notice:
This parameter must always be set to the same value on both CUDs!
Note:
If value = 0:
There is no quasi-synchronization of the analog inputs on the two CUDs. Connector outputs r52030[0 to 6] on both
CUDs always indicate a value of 0%.
If value = 1:
The analog inputs of the right-hand CUD are interpolated on the left-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the left-hand CUD. Connector outputs r52030[0 to
6] on the right-hand CUD always indicate a value of 0%.
If value = 2:
The analog inputs of the left-hand CUD are interpolated on the right-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the right-hand CUD. Connector outputs r52030[0 to
6] on the left-hand CUD always indicate a value of 0%.
If value = 3:
The analog inputs of the right-hand CUD are interpolated on the left-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the left-hand CUD.
The analog inputs of the left-hand CUD are interpolated on the right-hand CUD in such a way that 6 simultaneously
scanned values appear at the connector outputs r52030[0 to 6] of the right-hand CUD.
Description:
Setting to select the simulation of analog input 0 (X177.25/26) on the CUD.
Value:
0:
Simulation deactivated
1:
Simulation activated
Dependency:
Refer to: p50707
Note:
The setpoint for the simulation is set in p50707.
Description:
Sets the type for analog input 1 (X177.27/28) on the CUD.
Value:
0:
Bipolar voltage input (-10 V ... +10 V)
1:
Bipolar current input (-20 mA to +20 mA)
2:
Unipolar current input monitored (+4 mA to +20 mA)
Note:
AI: Analog Input
Description:
Sets the scaling for analog input 1 (X177.27/28) on the CUD.
p50709
CUD analog input 0 simulation selection / CUD AI 0 sim sel
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50710
CUD analog input 1 type / CUD AI 1 type
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2080
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
0
p50711[0...n]
CUD analog input 1 scaling / CUD AI 1 scal
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
2080
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-1000.0 [%]
1000.0 [%]
100.0 [%]