2 Parameters
2.2 List of parameters
SINAMICS DCM
510
List Manual (LH8), 02/2015, 6RX1800-0ED76
Description:
Sets the time constant for smoothing the signal from the "main actual value" analog input (XT1.103/104).
Description:
Sets the signal source for enabling the analog input for the "main actual value (XT1.103/104).
Note:
1 signal: Analog input enabled
0 signal: Analog input not enabled (r52013 = 0%).
Description:
Sets the setpoint for the simulation of the "main actual value" analog input (XT1.103/104).
Dependency:
Refer to: p50749
Note:
Simulation is selected using p50749 = 1.
Description:
Setting to select the simulation of the "main actual value" analog input (XT1.103/104).
Value:
0:
Simulation deactivated
1:
Simulation activated
Dependency:
Refer to: p50747
Note:
The setpoint for the simulation is set in p50747.
Description:
Sets the signal source for the output value at analog output 0 (X177.49/50).
p50745
Analog input main actual value smoothing time constant / AI m act T
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
p50746
BI: Signal source to enable analog input main actual value / AI m act ena sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p50747
Analog input main actual value setpoint simulation / AI m_actV sim setp
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
-130.0 [%]
130.0 [%]
0.0 [%]
p50749
Analog input main actual value simulation selection / AI m_actV sim sel
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Integer16
Dyn. index:
-
Func. diagram:
2075
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
p50750
CI: CUD analog output 0 signal source / CUD AO 0 sig s
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
-
Func. diagram:
2095
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0