SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
475
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the integral time (Tn) on the speed controller.
Description:
Sets the signal source for the droop on the speed controller.
Note:
A setting of 10% droop means that at 100% controller output (100% torque or current setpoint), the speed will deviate
from the setpoint by 10% ("softening" of closed-loop control).
Description:
Sets the x coordinate for pair of values 1 for adaptation of the P gain (Kp).
Notice:
The following condition applies for x coordinate 1/2:
p50556 < p50559
Note:
The adaptation of the P gain (Kp) is defined using 2 pairs of values.
Pair of values 1:
p50556/p50550 (x/y coordinate)
Pair of values 2:
p50559/p50225 (x/y coordinate)
Description:
Sets the x coordinate for pair of values 1 for adaptation of the integral time (Tn).
Notice:
The following condition applies for x coordinate 1/2:
p50557 < p50560
Note:
The adaptation of the integral time (Tn) is defined using 2 pairs of values.
Pair of values 1:
p50557/p50551 (x/y coordinate)
Pair of values 2:
p50560/p50226 (x/y coordinate)
p50554[0...n]
CI: Speed controller adaptation Tn signal source / Adapt Tn sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6805
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p50555[0...n]
CI: Speed controller adaptation droop signal source / Adapt droop sig s
DC_CTRL
Can be changed:
T
Calculated:
-
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Dyn. index:
CDS, p0170
Func. diagram:
6805
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
- -
0
p50556[0...n]
Speed controller adaptation Kp x coordinate 1 / Adapt Kp x1
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6805
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.00 [%]
100.00 [%]
0.00 [%]
p50557[0...n]
Speed controller adaptation Tn x coordinate 1 / Adapt Tn x1
DC_CTRL
Can be changed:
U, T
Calculated:
-
Access level:
2
Data type:
FloatingPoint32
Dyn. index:
DDS, p0180
Func. diagram:
6805
P-Group:
-
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
PERCENT
Expert list:
1
Min Max
Factory
setting
0.00 [%]
100.00 [%]
0.00 [%]