SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
129
2 Parameters
2.2 List of parameters
Note:
If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then
p2037 should be set to 2.
Description:
Sets the interface mode of the PROFIdrive control words and status words.
When selecting a telegram via p0922 (p2079), this parameter influences the device-specific assignment of the bits in
the control and status words.
Value:
0:
SINAMICS
2:
VIK-NAMUR
Dependency:
Refer to: p0922, p2079
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the serial interface for the debug monitor.
With p2039 = 1, the serial interface COM2 (X179) is set.
Other values are not permitted.
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Note:
p2040 = 0:
Monitoring is de-activated.
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
SINAMICS
1:
VIK-NAMUR
Note:
Every change only becomes effective after a POWER ON.
p2038
IF1 PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 2
0
p2039
Select debug monitor interface / Debug monit select
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
4
Data type:
Unsigned16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 3
1
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dyn. index:
-
Func. diagram:
9310
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
1999999 [ms]
100 [ms]
p2042
PROFIBUS Ident Number / PB Ident No.
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
-
P-Group:
Communications
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
Summary of Contents for SINAMICS DCM
Page 1: ...s SINAMICS SINAMICS DCM List Manual 02 2015 Edition Answers for industry ...
Page 2: ......
Page 1192: ...A Appendix A 2 List of abbreviations SINAMICS DCM 1192 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1202: ...Index SINAMICS DCM 1202 List Manual LH8 02 2015 6RX1800 0ED76 ...
Page 1203: ......