2 Parameters
2.2 List of parameters
SINAMICS DCM
164
List Manual (LH8), 02/2015, 6RX1800-0ED76
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification (see the List Manual, chapter
"Faults and alarms").
Example:
F12345 and fault response = OFF3 (OFF1, OFF2, NONE)
--> The default fault response OFF3 can be changed to OFF1, OFF2 or NONE.
Re value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
Re value = 2 (OFF2):
Internal/external pulse inhibit.
Re value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
Parameter values designated as "reserved", act just like the value = 2 (OFF2)
Description:
Sets the fault response for the selected fault.
Value:
0:
NONE
Dependency:
The fault is selected and the required response is set under the same index.
Notice:
For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description:
Sets the signal source to acknowledge all faults at all drive objects of the drive system.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
Description:
Sets the first signal source to acknowledge faults.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
p2101[0...19]
Change fault response response / Chng resp resp
TM150, TM15DI_DO,
TM31
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Integer16
Dyn. index:
-
Func. diagram:
8050, 8075
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 0
0
p2102
BI: Acknowledge all faults / Ackn all faults
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
2546, 8060
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0
p2103
BI: 1. Acknowledge faults / 1. Acknowledge
CU_DC, CU_DC_R,
CU_DC_R_S,
CU_DC_S, TM150,
TM15DI_DO, TM31
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
-
Func. diagram:
-
P-Group:
Messages
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
0