SINAMICS DCM
List Manual (LH8), 02/2015, 6RX1800-0ED76
101
2 Parameters
2.2 List of parameters
Note:
For drives with closed-loop speed control (p50084 = 1), the following applies:
- BI: p0840 = 0 signal: OFF1 (braking with the ramp-function generator, then pulse suppression and switch-on inhibit)
For drives with closed-loop torque control (p50084 = 2), the following applies:
- BI: p0840 = 0 signal: immediate pulse suppression
For drives with closed-loop speed/torque control, the following applies:
- BI: p0840 = 0/1 signal: ON (pulses can be enabled)
Description:
Sets the first signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switch on inhibit)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- No OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the second signal source for the command "No coast down/coast down (OFF2)".
The following signals are AND'ed:
- BI: p0844 "No coast-down / coast-down (OFF2) signal source 1"
- BI: p0845 "No coast-down / coast-down (OFF2) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 1 (STW1.1).
BI: p0844 = 0 signal or BI: p0845 = 0 signal
- OFF2 (immediate pulse suppression and switch on inhibit)
BI: p0844 = 1 signal and BI: p0845 = 1 signal
- No OFF2 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is effective.
p0844[0...n]
BI: No coast-down / coast-down (OFF2) signal source 1 / OFF2 S_src 1
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
2580
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1
p0845[0...n]
BI: No coast-down / coast-down (OFF2) signal source 2 / OFF2 S_src 2
DC_CTRL,
DC_CTRL_R,
DC_CTRL_R_S,
DC_CTRL_S
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
Unsigned32 / Binary
Dyn. index:
CDS, p0170
Func. diagram:
2580
P-Group:
Commands
Unit group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
1