Outputs
48
Siemens Building Technologies
Fire Safety & Security Products
07.2009
8.2.24 Walk
Test
Walk Test
This output is activated if a walk test for the assigned partition is performed via the engineer menu or the
user menu. It is reset:
z
when the test is ended,
z
when the partition is set,
z
after a time-out of 2 hours,
z
on an alarm.
8.2.25 Latching Sensor Reset
Sensor Reset
(Latching Sensor Reset)
z
This output is activated for 5 seconds in the assigned partition, when a user with a valid PIN is pressing at
the remote keypad the “X” button.
z
This Output can be used to reset detectors with available alarm memory.
z
This output is also activated for 5 seconds in the assigned partition, when a user is exiting the engineer
menu.
Assumption: An alarm has to be triggered from a detector (glass break, fire).
8.2.26 Door Lock Pulse
Door Lock Pulse
This output is activated for 5 seconds when the corresponding partition is being switched to full set.
8.2.27 Door Unlock Pulse
Door Unlock Pulse
This output is activated for 5 seconds when the corresponding partition is being switched to unset.
8.2.28 Buzzer
Buzzer On
NOTE
If the control panel is set using the keypad (and there is a "cannot set situation"), there will be
no output activation, but the message “Arming Impossible” will be displayed on the keypad.
NOTE
In combination with an SAK84/94 the buzzer is activated for 1.5 seconds.
This output is activated in the following cases depending on the setting of the buzzer parameters for this
output. The buzzer can be activated on:
E: Entry Time
The buzzer is activated during the entry time (continuous tone) after triggering a delayed input
X: Exit Time
The buzzer is activated during the setting delay (continuous tone).
When a delayed input is triggered, the continuous tone changes to an intermittent tone (on/off) until all de-
layed inputs are in quiescent state.
A: Alarm
The buzzer is activated on an alarm (continuous tone).
S: Full Set Confirmation
The buzzer is activated for 3 seconds on a positive acknowledgement or outputs for 3 or 6 short buzzes on a
negative acknowledgement
C: Chime
The buzzer is activated for a short beep and the "Chime" output for one pulse.
NOTE
The chime can be switched on/off by user only for the default partition assigned to a keypad
address. Chime function in other partitions are still activated and can not be switched of. There-
fore it’s recommended to use chime function only in 1 particular partition.
F: Fire
The buzzer is activated on a fire alarm (alternating, 2 seconds on and 1 second off)
R: RF
The buzzer is activated for a short buzzes when the system will be full set by RF remote control.