6.3.34 Emergency Exit 1-5 (SI120: Emergency Exit 1-2)
Emergency Exit 1
For the logical type "Emergency Exit" also the physical type "Emergency Exit" must be se-
lected.
On unset: emergency exit alarm in the assigned partition.
On part set: Direct triggering in the assigned partition.
On full set: Direct triggering.
On unset an emergency exit alarm is triggered which activates the buzzer and the name of the input is
displayed on the remote keypad LCD. The "emergency exit 1" output is also activated for the programmed
time. The alarm can be reset by inputting a valid PIN and pressing the "X" key, or by short-circuiting the
input. For this reason, the mode using two terminating resistors is absolutely mandatory for this input type.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1
X
External
bell
X
2
Internal
bell
1
X
Strobe
light
X
X
Cannot full set
X
Cannot part set
X
X
Alarm in memory
X
X
Block lock not released
X 5 5 Buzzer
X
Emergency exit
3
X
Burglar alarm system transmission line
3
X
Burglar alarm partition transmission line
3
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
3 =
Triggering only if "transmission" parameter is chosen.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
Emergency exit 2
As "Emergency Exit 1" with effect on "Emergency Exit 2" output.
Emergency exit 3
As "Emergency Exit 1" with effect on "Emergency Exit 3" output (SI220 only)
Emergency exit 4
As "Emergency Exit 1" with effect on "Emergency Exit 4" output (SI220 only)
Emergency exit 5
As "Emergency Exit 1" with effect on "Emergency Exit 5" output (SI220 only)