Keypads
61
Siemens Building Technologies
Fire Safety & Security Products
07.2009
10 Keypads
[TM514] Remote Key-
pads
This menu function enables the following parameters to be programmed for each remote keypad.
z
Partition assignment in idle state (basic partition)
z
Security stage
z
Remote keypad type: normal/intellectual lock
z
Remote keypad buzzer
z
Setting without code
10.1 Default
Partition
Partition Assignment in
Idle State
The LEDs of the remote keypads can only indicate the status of one partition. But because several partitions
can be controlled from one remote keypad, it is necessary to define which partition the LEDs indicate in the
idle state. Immediately a valid user PIN is entered and a partition is selected, the status of this partition is
immediately indicated.
10.2 Keypad
Mode
Keypad Mode
In this menu it’s defined, if the remote keypad is used as a "normal" remote keypad or as a "GV Geistiger
Verschluss” (IL Intellectual Lock) keypad.
Internal = The keypad works
Normal
without linking operation to GV input function.
External = The keypad works in combination with GV(IL). In this case the keypad operation is only acces-
sible with the 2
nd
identification within 20 seconds, when the GV was triggered.
10.3 LEDs
Keypad
LEDs Keypad
LCD
Input status LCD
LED
This parameter must always be set on.
Not relevant
Not relevant
10.4 Buzzer
On
NOTE
In combination with an SAK84/94 the buzzer is activated for 1.5 seconds.
I: Entry Time
The buzzer is activated during the entry time (continuous tone) after triggering a delayed input
O: Exit Time
The buzzer is activated during the setting delay (continuous tone).
When a delayed input is triggered, the continuous tone changes to an intermittent tone (on/off) until all de-
layed inputs are in quiescent state.
A: Alarm
The buzzer is activated on an alarm (continuous tone).
C: Full Set Confirmation
The buzzer is activated for 3 seconds on a positive acknowledgement or outputs for 3 or 6 short buzzes on a
negative acknowledgement
H: Chime,
The buzzer is activated for a short beep and the "Chime" output for one pulse.
NOTE
The chime can be switched on/off by user only for the default partition assigned to a keypad
address. Chime function in other partitions are still activated and can not be switched of. There-
fore it’s recommended to use chime function only in 1 particular partition.