Engineer Management
89
Siemens Building Technologies
Fire Safety & Security Products
07.2009
19.3.5 Unreset
Counter
[TM35] Unreset Counter
This menu shows the number of alarm who have occurred from the beginning. This counter can't be reset,
except with a factory reset.
19.4 Engineer
Reset
These functions are explained in the menu 12"System".
19.5 System
Programming
These functions are explained in the menu 12"System".
19.6 Telecom
Options
These functions are explained in the menu 13 "ARC".
19.7 Time
Functions
These functions are explained in the menu 3"Miscellaneous".
19.8 Tests
19.8.1 Walk
Test
[TM81] Walk test
This menu function enables a walk test to be carried out in the individual partitions. The walk test activates
the walk test outputs. In the event of a walk test alarm the buzzer or internal bell, as selected, is activated
briefly. A walk test can naturally only be carried out with the inputs which are unset. Set inputs, e.g. inputs
monitored for 24 hours, immediately trigger a real alarm. Otherwise, the line test must used.
Partitions
The walk test is carried out per partition.
Buzzer activation
This parameter allows not only the buzzer to be briefly activated during the walk test, but also the internal
bell.
Walk test outputs
During the walk test, all the outputs programmed for the walk test in this partition are activated.
[TM52] Delete storing
messages outputs
After a walk test alarm, all the outputs in this partition programmed as "Delete storing messages" are briefly
activated.
Timeout
The walk test is limited to 2 hours by a timeout.
19.8.2 Input
Test
[TM82] Test of inputs
This menu function enables each individual input in the individual partitions to be tested. By means of this
test, the actual state or triggering and resetting can be tested. By storing or transfers from idle to the trig-
gered state or the other way round, individual inputs can be triggered locally and subsequently checked by
triggering at the central control unit. The input which is on test is switched off during the test, e.g. it does not
trigger a real alarm but instead only the status is indicated on the LCD display and the buzzer or inner bell is
briefly activated as chosen. The resistance value or the quality of the radio transmission is also indicated.
Partitions
The choice of partition limits the test to this partition.
Buzzer activation
This parameter enables not only the buzzer to be briefly activated during a walk test but also the internal bell.
Actual state
The actual state of the input is indicated on the LCD keypad.
Stored information
The changeover from idle state to the triggered state or the other way round is shown in the display.
Reset
The stored information can be deleted by pressing the X key, which also causes the test of this input to be
halted. If the test of this input is to be continued, this input must again be confirmed.
Symbols
The states or change of states are indicated as follows. (useful for single person testing)
= Input actually in idle state,
= Input actually in triggered state,