Inputs
26
Siemens Building Technologies
Fire Safety & Security Products
07.2009
6.3.18 Technical
Alarm
NOTE
The technical alarm is displayed after deactivation of an active input at the logical state within Sylcom
"Alarm in memory". This flag can be reset by an engineer reset.
Technical Input
(Technical Zone)
Acts on all technical outputs, remote keypad buzzers and remote keypad alarm LED’s of the assigned
partition regardless of the setting. No alarm memory is set, but instead the alarm is written only to the
memory. Immediately the input is again in its normal state, the technical outputs, remote keypad buzzers
and remote keypad LED’s are reset.
With this input, the delay time acts as an activation time of the input before a technical alarm is triggered.
Examples:
Delay time zero
Æ
direct triggering.
Delay time = 5 seconds
Æ
The input must be activated for more than 5 seconds in order for it to be
triggered.
Input triggered
Æ
Technical alarm in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
5 5 5 Buzzer
X X X Technical
X X X Technical
transmission
line
X
X
X
Technical partition transmission line
X
X
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
6.3.19 Remote
Assistance
Remote Assistance
Direct triggering of a remote assistance transmission in assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
X
X
X
Remote assistance transmission line
X
X
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.