System
67
Siemens Building Technologies
Fire Safety & Security Products
07.2009
12.5 Summer/Winter
Time
Change
[TM72] Change date
and time
This menu function is used to change the date and time. The clock is immediately updated after confirmation.
The hours must be entered using the 24 hour system. The change of date and time is written to the log.
12.6 Sylcom Access when Set
This parameter allows or denies a remote access by a full set system.
12.7 Up/Download
Mode
[TM65] Up/download
if set
This parameter defines whether or not access is permitted via Sylcom (local or remote) on part set or full set.
z
U = Up/download permitted,
z
- = Up/download not permitted.
Access options
This parameter defines the access security for an up/download.
No up/download
No up/download possible, Control panel rejects all actions requested by Sylcom.
1 = Level 1
Control panel accepts all actions from Sylcom without local authorization by the user:
z
Direct call by Sylcom without user authorization,
z
Callback to a free number without local user authorization,
z
Callback to programmed number without local user authorization,
2 = Level 2
Control panel accepts all actions with local user authorization. Without user authorization only callback to
pre-programmed number (Service 1).
z
Callback to a free number with local user authorization,
z
Callback to programmed number without local user authorization.
3 = Level 3
Control panel accepts only callback to pre-programmed number (Service 1) with local user authorization.
z
Callback to programmed number with local user authorization.
NOTE
Callback function is not possible over IP!
12.8 Delay
Supervision
[TM5173] Radio monitor-
ing
Delay between 2 supervisons can be set in following way. Defined time depends on the RF gateway type.
SiRoute SiWay
Long 27h
4h
Medium 18h
2h
Short 9h
1h
Very short
4h30
30mn
12.9 RF
Supervision
[TM5173] Radio monitor-
ing
This parameter determines how to handle a RF device fault. If a device is missing you can choose between
tamper alarm, trouble or no supervision
z
"No" = The central control unit does not detect that a radio alarm no longer exists for whatever reason.
z
"As a Tamper" = The central control unit triggers a tamper alarm if for whatever reason one no longer
exists.
z
"As a Trouble" = The central control unit triggers a fault if for whatever reasons one no longer exists
Summary of Contents for SI120