System
66
Siemens Building Technologies
Fire Safety & Security Products
07.2009
12.4.3 Sintony
Telephone
[TM65] Control Panel
Telephone Number
The Sintony telephone number must only be set when a remote access is needed.
NOTE
For this function, either the SML 51 or the SML 61 module must be installed.
12.4.4 MSN
Number
The Sintony MSN number must be the same number as the “Sintony Telephone”
number when an ISDN remote access is needed.
NOTE
For this function, the SML 61 module must be installed.
12.4.5 Number of Attempts
[TM65] Number of dial-
ling attempts
This parameter defines the number of dialing attempts before a transmission error is triggered. A value be-
tween 1 and 12 can be entered.
12.4.6 Number of Rings
[TM65] Number of rings
This parameter defines the number of rings before Control panel occupies the line on a call.
Values from 0 to 5 can be entered. Value 0 means that the line is, in principle, not occupied on a call, but in
order to enable an up/download by the user in this case, the line is occupied after the first call during the 10
minutes after the user authorization, provided value 0 is programmed.
12.4.7 Dialling
Method
[TM65] Dialling method
This parameter defines the dialing method used for the telephone connection.
z
P = Pulse, pulse method (slow),
z
T = Tone, multifrequence method (fast).
12.4.8 Line Monitoring
[TM65] Line monitoring
This parameter defines whether the line monitoring is switched on or off. The line is occupied and monitored
for dialing tone. Intervals of 5 min., 30 min., 12 h or 24 h may be chosen.
-
- - = no line monitoring.
Phone Line Supervision (PSTN)
SI120
Line Supervision can be set to No - 5 or 30 min. - 12 or 24 h To enable it, the parameter has to be set to a
value different of ‘No’. After the defined time, Line Supervision is performed. If the line is not connected or
working a trouble message is generated at the keypad: “Trouble Com. Supervision” The following Line Su-
pervision will take place 15 min. after.
SI220
Same management like in SI120. But additionally, the Line Supervision can be done also using SML21. In
this case, and if the parameter is different of ‘No’ (whatever the value 5 min., 30 min., 12 h or 24 h), the Line
Supervision will be performed every minute. If the line is not connected or working a trouble message is
generated at the keypad: “Trouble Com. Supervision”. If the line is ok within 1 min. trouble disappears.
Phone Line Supervision (ISDN)
SI120/SI220
To enable it, the parameter has to be set to a value different of ‘No’ (whatever the value 5 min., 30 min., 12 h
or 24 h).
If the line is not connected or working, there is immediately on SML61 activation of the yellow LED. After 1’30
min. a trouble message is generate at keypad: “Trouble Com. Supervision”. As soon as the line is ok all
troubles disappear.