Engineer Management
92
Siemens Building Technologies
Fire Safety & Security Products
07.2009
19.8.7 Setting
Test
[TM87] Setting test
This menu function enables a test setting. The partition “cannot set” situation will be ignored (nevertheless
“cannot set” led keeps on). This means that a partition can also be set with persons present in the protected
partition.
Enable
Enable The test setting is performed per partition. The specific partition has to be set during the next 10
minutes and only one setting is allowed. If the partition is not set before 10 minutes or after the unsetting of
the partition, the central control unit returns to the normal state.
19.8.8 Autotest
Start autotest 1[TM671] / Start autotest 2[TM672]
Delay autotest
The start of the automatic test call 1 can be defined here by entering an offset time. The first test call is then
started after the time entered here. The delay can be entered in hours and minutes (maximum 23 hours 59
minutes). If the value 00 hours 00 minutes is entered, the first test call is transmitted after the time of the test
period programmed in the ARC menu "Automatic Test".
Start time
The sequence of programming the test period and the offset are important for the start time. The start times
for the first test are shown in the following table, with the auto test being programmed first.
Auto test, period
changed / confirmed
Offset
Hrs./min.
Start time of first test
No
-
After end of current time interval.
Yes
-
1 minute after leaving the engineer menu, then after time interval.
Yes / No
00H 00M
Time interval starts after confirmation of offset Þ first test after time
interval.
Yes / No
02H 00M
2 hours after confirmation of offset, then after time interval.