System Input Transmission
83
Siemens Building Technologies
Fire Safety & Security Products
07.2009
074: Technic alarm
Is transmitted if a technical alarm has been triggered in the system. Clear message after the end of the
technical alarm.
075: Burglar alarm
Is transmitted if a burglar alarm has been triggered in the system (in one of the partitions). Clear message
in accordance with the programming of the "Partitions system options" (TM53) and "Clear message" pa-
rameters in the engineer menu.
076: unused
System input 076 has no function.
077: Tamper alarm
Is transmitted if a tamper alarm has been triggered in the system (in one of the partitions). In contrast to
the system tamper transmission; this line is also transmitted if one of the inputs with the tamper line type is
transmitted. This means that a transmission takes place under the following conditions.
z
Open central control unit or open E-bus components
z
Loss of E-bus components
z
Tamper of inputs with two terminating resistors
z
Tamper with programmed inputs.
Clear message for system tamper on alarm reset, for alarm inputs in accordance with the "Partitions Sys-
tem Options" TM53) and "Clear message" parameters in the engineer menu.
078: Fire alarm
Is transmitted if a fire alarm has been triggered in the system (one of the partitions). Clear message on
alarm rest.
079: Duress PIN
Is transmitted if a duress PIN has been entered (code PIN +2).
080: PIN Tamper
Is transmitted after 3 consecutive wrong code entries on the keypad.
081: Line Fault
Is transmitted if the telephone line is interrupted or the voltage drops below 20V.
Clear message when the line is again restored.
082: Remote Assistance
Transmitted if an input programmed to remote assistance is triggered or if a remote assistance is triggered
via and SAK (press key
?
three times). Clear message directly after remote assistance transmission.
083: Call detection
Is transmitted if the control panel has detected an incoming call.
084: Buying Time
Is transmitted if “Buy Time” action has been performed in the system.
085 – 144: Partition 1-6->
(X)
Part set P(X)
Is transmitted if partition 1 is set to part set. Clear message when partition 1 unset.
Full set P(X)
Is transmitted if partition 1 is set to full set. Clear message when partition 1 unset.
Restr. Full Set P(X)
Is transmitted if partition 1 is set to full set, but at least one input (line) is bypassed. Clear message when
the line is again restored (see "Partitions system options" (TM53), "Forced set options" parameters in the
engineer menu) or when partition 1 unset.
Complete full set P(X)
Is transmitted if the complete partition 1 (no input bypassed) is full set. Clear message when partition 1
unset.
Abort / confirm P(X)
Is transmitted if an alarm has been cancelled in partition 1 (see transmission verification method).
Technic alarm P(X)
Is transmitted if a technical alarm was triggered in partition 1. Clear message after end of technic alarm.
Burglar alarm P(X)
Is transmitted if a burglar alarm has been triggered in partition 1. Clear message in accordance with "Parti-
tions system options" (TM53) and "Clear message" parameters in engineer menu.
Panic alarm P(X) (D, CH,
F, ES)
Is transmitted if a panic alarm or a silent panic alarm was triggered in partition 1. Clear message after 10
seconds.
Panic alarm P(X) (UK)
Is transmitted if a panic alarm or a silent panic alarm was triggered in partition 1. Clear message on alarm
reset.
Tamper alarm P(X)
Is transmitted if a tamper alarm has been triggered in the partition 1 (in one of the partitions). In contrast to
the partition 1 tamper transmission, this line is also transmitted if one of the inputs with the tamper line type
is transmitted. This means that a transmission takes place under the following conditions.
z
Open central control unit or open E-bus components
z
Loss of E-bus components
z
Tamper of inputs with two terminating resistors
z
Tamper with programmed inputs.
Clear message for partition 1 tamper on alarm reset, for alarm inputs in accordance with the "Partitions
System Options" TM53) and "Clear message" parameters in the engineer menu.
Fire P(X)
Is transmitted if a fire alarm has been triggered in the partition 1 (one of the partitions). Clear message on
alarm rest.