Inputs
27
Siemens Building Technologies
Fire Safety & Security Products
07.2009
6.3.20 Fire
Fire Alarm
This input will be needed, if a fire warning detector is connected. Shortcut will be detected as an alarm,
4,7 k
Ω
= Line OK; broken wire = signaled not as a tamper but as a fault. Acts on the fire bells regardless
of the setting. The burglar alarm bells can also be activated.
NOTE
Therefore the physical input type must be set to „fire detector“.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1 1 1 External
bell
2 2 2 Internal
bell
X X X Fire
alarm
X X X Alarm
in
memory
5 5 5 Buzzer
X X X Fire
transmission
line
X
X
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
IMPORTANT
The fire zones and its connected fire detectors are only used as fire warning
devices. The intrusion control unit is not replacing a fire alarm system.
6.3.21 Tamper
Tamper Alarm
Direct triggering of a Tamper in assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1 X
External
bell
X X 2 Internal
bell
1 X
Strobe
light
X
X
Cannot full set
X
Cannot part set
X X X Alarm
in
memory
X
X
Block lock not released
5 5 5 Buzzer
X
X
X
Transmission line tamper
X
X
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.