Inputs
29
Siemens Building Technologies
Fire Safety & Security Products
07.2009
6.3.24 BA Full Set only
Burglar Alarm Full Set only
Brief description: BA external; internal inactive
On part set: No triggering in the assigned partition.
On full set: Direct triggering in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
X
External
bell
X
Strobe
light
X
X
Cannot full set
X
Alarm in memory
X
X
Block lock not released
5 Buzzer
X
Burglar alarm system transmission line
X
Burglar alarm partition transmission line
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
6.3.25 BA Full or Part Set
Burglar Alarm Full/Part Set
Brief description: BA external; internal
Direct triggering on Part and Full set in the assigned partition.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1 X
External
bell
X
2 Internal
bell
1 X
Strobe
light
X
X
Cannot full set
X
Cannot part set
X
X
Alarm in memory
X
X
Block lock not released
5 5 Buzzer
3
X
Burglar alarm system transmission line
3
X
Burglar alarm partition transmission line
3
X
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
3 =
Triggering only if "transmission" parameter is chosen.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.