Partitions
55
Siemens Building Technologies
Fire Safety & Security Products
07.2009
9.4.3 By
Fire
External Bell / Fire
This parameter defines whether or not the external bell is enabled in the event of a fire warning alarm (alter-
nating 2 seconds ON, 1 second OFF).
Yes = Enabled (Activation time defined by External Bell Dureation (not fire bell duration)
No =
Disabled
9.4.4 RF
Confirm
External Bell on RF
If this parameter is activated, the external bell indicates the arming confirmation if partition is set or unset by
radio remote control. Radio-setting is indicated with 2 short pulses, unsetting with only one pulse.
Yes = Enabled
No =
Disabled
9.5 Internal
Bell
9.5.1 When
Full
Set
Internal Bell Mode
This parameter defines whether or not the internal bell is enabled in the event of a burglar alarm On full set:.
This parameter also acts on the strobe light output.
Yes = Enabled
No =
Disabled
9.5.2 Duration
Internal Bell Duration
This parameter defines the maximum triggering time of the internal bell output in the event of an alarm.
Times from 000 to 127 seconds or minutes can be entered (000 continuous).
This timer runs only for outputs with logical type “Internal Bell”.
9.5.3 By
Fire
Internal Bell/Fire
This parameter defines whether or not the external bell is enabled in the event of a fire warning alarm (2
seconds ON, 1 second OFF).
Yes = Enabled. Activation time defined by Internal Bell Dureation (not fire bell duration)
No =
Disabled
9.6 Fire
Bell
Fire Bell Mode
This parameter defines whether or not the fire warning bell is continuously or intermittently enabled in the
event of a fire warning alarm:
F = Fixed
(continuous)
I = Intermittent (2 seconds ON, 1 second OFF).
.
IMPORTANT
The fire zones and its connected fire detectors are only used as fire warning
devices. The intrusion control unit is not replacing a fire alarm system