Inputs
34
Siemens Building Technologies
Fire Safety & Security Products
07.2009
6.3.33 BA Loop Follower Full or Part Set
Burglar Alarm Follower
Full / Part Set
Brief description: BA external entry follower; internal entry follower
Delayed exit triggering on Part and Full set in the assigned partition and a possible delayed entry triggering
to another BA Input in the same partition. If no other BA Input is triggered, an immediate BA will take place
on the Loop Follower Input.
NOTE
The parameter “delay” applies only on the exit delay time.
DE, UK
If on setting the input remains triggered up the end of the delay time, the partition is again unset.
All other country ver-
sions
If on setting the input remains triggered up the end of the delay time, the partition remains full set and an
alarm is triggered.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
1/4
4 External
bell
4 2/4
Internal bell
1/4
4 Strobe
light
8
8
Cannot full set
8
Cannot part set
4
4
Alarm in memory
X
X
Block lock not released
4/5
4/5
Buzzer
3/4
4
Burglar alarm system transmission line
3/4
4
Burglar alarm partition transmission line
Partition parameters:
X =
Triggering regardless of the partition mode.
1 =
Triggering only if the external bell “When Part Set” in the partition parameter is chosen.
2 =
Triggering only if the internal bell “When Full Set” in the partition parameter is chosen.
3 =
Triggering only if "transmission" parameter is chosen.
4 =
Triggering delayed if a delayed input has already been triggered.
5 =
Triggering only if “Buzzer On” in the keypad parameter is chosen.
8 =
Triggering only if no exit delay is programmed.