Page 104
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Mo
dbus
Reg
ist
er T
ypes
The decimal offset indicates how the remote system must interpret the integer value that
is stored in the parameter access register. The following table shows how different
parameter values can be shown based on a register value (integer) of 1234.
Examples of using the format word for both the index values and the decimal offset value
are shown below:
To write these values you can use a decimal offset as follows: format word = (primary
index x 1000) + (secondary index x 10) + (decimal).
Decimal
Offset
Example
0
0
1,234
1
–1
12,340
2
–2
123,400
3
–3
1,234,000
4
–4
12,340,000
5
–5
123,400,000
6
+1
123.4
7
+2
12.34
8
+3
1.234
9
Percent
12.34%
Format
Primary Index
Secondary Index
Decimal
00000
00
00
0
01003
01
00
3 right
02038
02
03
3 left
05159
05
15
percent